DB 2 SE TC A180 FS2 FGR
Application
Diatermal oil boiler To=300°C , Pmax 1340 kW - three pass boiler
Regenerator for combustion air preheater (air temperature =140°C)
Customer demand
Replacement of old burner and emissions upgrade to fulfill the requirement of max limit of Nox=100mg/Nm3 at 3%O2 (DLGS183/17)
Released configuration
- Dual bloc burner with specific arrangement fo comburent air up to 150°C
- Operating wih Natural gas
- Burner configurations for induced draft of recirculated flue gasses (drawn from downstream the regenerator and injected upstream the comburent air fan)
- Automatic correction of Air /fuel ratio in function of the residual O2 content in the flue gas
- Ignition with gas pilot burner and combustion head designe and optimized to operate with flue gas recirculated up to 10%
- Flame detection by IR sensor
- Burner configuration and controls for continuous operation